Appendix G: Specifications

This appendix provides electrical and environmental specifications for the XT+ Extinguishant Control Panel. Current levels provided in the tables of this appendix are maximum ratings unless otherwise indicated.

Operating Constraints

Installation of the XT+ Extinguishant Control Panel must include the operating constraints of the system to maintain continuous signal monitoring and reporting. Operating constraints are based on the current-driving capability of the panel while maintaining external loading caused by devices and cabling.

External loading must be selected within the limits of the XT+ Extinguishant Control Panel to provide continuous operation. External loading is caused by individual or multiple combinations of Signaling Line Circuits, Notification Appliance Circuits, and Initiating Devices. It is also caused by the size and length of cabling connections. Refer to Calculations to determine the appropriate size and length of cabling.

Electrical

AC Input Ratings

Terminal

Description

Power Supply

Power

L

 

AC line

 

5.25 A

1.83 Amps Max @ 115 V, 50/60 Hz
0 .915 Amps Max @ 230 V, 50/60 Hz

10.25 A

2.5 Amps Max @ 115 V, 50/60 Hz
1.25 Amps Max @ 230 V, 50/60 Hz

N

AC neutral

 

 

W

Ground

 

 

AC line and AC neutral terminals are supervised for open and short circuits, provided standby batteries are functional.

Power Supply

Fuses

Power Supply

Description

5.25 A

AC Input, 3 A, 250 VAC, slow blow, 5 x 20 mm

10.25 A

AC Input, 5 A, 250 VAC, slow blow, 5 x 20 mm

24 VDC Output Ratings

Designation

Description

Output voltage

22V DC minimum, 26.4V DC maximum

Ripple Voltage

1 V Maximum

Maximum Standby Current

Rated maximum output current which can be supplied continuously in normal standby.

     S406 5.25A Power Supply

1.9 A

     S408 10.25A Power Supply

3.4 A

Maximum Alarm Current Rated maximum output current which can be supplied in alarm.

     S406 5.25A Power Supply

4 A

     S408 10.25A Power Supply

8 A

Standby Battery Ratings

Designation Description

AH max

Maximum battery capacity in amp hours for 5.25 A and 10.25 A Power Supplies

     5.25 A

60 AH maximum

     10.25 A

100 AH maximum

Ri max

Maximum series resistance in battery charging circuit before a trouble is indicated.

     5.25 A

1 Ohm

     10.25 A

0.4 Ohm

Ground Trouble Indication

A ground trouble indication occurs on the XT+ Extinguishant Control Panel when 30K Ohms or less exists between the ground and either DC RTN or +24 VDC of the power supply.

System Power

When AC power is present, the system operates entirely from AC power (primary). During an AC power failure, the entire system load is transferred to the standby batteries (secondary).

Standby and Alarm Current

Standby and Alarm Currents of the XT+ Extinguishant Control Panel with two loops are provided below. Two loop operation includes System A Panel Module, System B Panel Module, and the Dual Loop Panel Module. Two loop operation represents the minimum board configuration of the XT+ Extinguishant Control Panel. The data excludes all external loads. Primary loads assume a fully charged battery.

5.25 A Power Supply

Standby Load (mA)

Alarm Load (mA)

Description

244 mA @ 115 VAC

272 mA @ 115 VAC

Line current for standby and alarm when battery charge current is less than 30 mA.

162 mA @ 230 VAC

177 mA @ 230 VAC

Line current for standby and alarm when battery charge current is less than 30 mA.

560 mA @ 24 VDC

650 mA @ 24 VDC

Battery current for standby and alarm when AC power failure condition is present.
10.25 A Power Supply

Standby (mA)

Alarm (mA)

Description

220 mA @ 115 VAC

234 mA @ 115 VAC

Line current for standby and alarm when battery charge current is less than 30 mA.

176 mA @ 230 VAC

181 mA @ 230 VAC

Line current for standby and alarm when battery charge current is less than 30 mA.

550 mA @ 24 VDC

620 mA @ 24 VDC

Battery current for standby and alarm when AC power failure condition is present.

The data provided above for standby and alarm current includes loads of a two loop fire control panel alone and excludes current loads from external devices or equipment.

Battery

Rechargeable Standby Battery Circuit

Designation

Description

Standby Battery Type

Two 12 VDC, rechargeable, valve-regulated, lead-acid batteries wired in series

Charger Type Temperature compensated, current limited float charger

Low Battery Disconnect Voltage

19 V (+/- 1 volt)

Standby Battery Capacity

Installation-dependent. Refer to Determining the Standby Battery Capacity to determine the amp hour rating of the standby batteries.

Standby Battery Charge Voltage

27.6 V nominal, temperature-compensated and current-limited

Charge Current

Maximum charging current of standby batteries.

5.25 Amp Power Supply

1.25 A

10.25 Amp Power Supply

2.25 A

Standby Battery Loads

Standby battery loads are generated by measuring the series battery current of the power supply following a power failure condition. Standby and alarm current of the XT+ Extinguishant Control Panel can include all or part of the following loads:

Loads

Standby Current

Alarm Current

5.25 A Power Supply

78 mA

78 mA

10.25 A Power Supply

80 mA

80 mA

Dual Loop Panel Module

115 mA

115 mA

NAC Outputs

0 mA (per output)

2500 mA (per output)

XT+ Extinguishant Control Panel *

350 mA max

450 mA max

335 mA typical 435 mA typical

Zone LED Module

5 mA

5 mA + 3 mA per LED

XT+ Network Module

80 mA

80 mA

XT+ Printer

0 mA

1500 mA (only during printing)

* LCD Main Processor Board, Main Back Board, System A Panel Module, System B Panel Module

Cabling

Specify cabling that meets or exceeds NFPA 72 and UL 864 guidelines.

Cable Maximum Parameters for Network

Property

Ratings

Resistance

100 Ω total for both conductors

Core to Core Capacitance

300 nF

Core to Screen Capacitance

450 nF

Inductance Per Core

600 µH

RS-485 Serial Data and Terminal Capacity

Property

Description

Serial Data Connection

up to 3900 feet of 18/2 FPLR

Maximum Terminal Capacity

14 AWG

Cable Maximum Parameters 25 Ω per conductor, 600 µH per conductor, 300 nF

SLC Loop Ratings

The following ratings represent Hochiki DCP Protocol SLC loops of the XT+ Extinguishant Control Panel.

Connection

Rating

LOOP ( - OUT ), ( + OUT )

36 V DC @ 400 mA

LOOP ( - IN ), ( + IN )

36 V DC @ 400 mA

Maximum Cable Capacitance: 1 µF

Maximum Wiring Voltage Loss: 6.4 V

Refer to SLC Loop Cabling for maximum allowable cable length calculations.

 

Main Back Board

NAC Outputs

NAC Outputs

Terminal

NAC 1

( + ), ( - )

NAC 2

( + ), ( - )

NAC 3

( + ), ( - )

NAC 4

( + ), ( - )

NAC 1 and 2 can be configured to provide one Class A circuit (NAC 1&NAC 2) or two Class B circuits (NAC 1 and NAC 2).

NAC 3 and 4 can be configured to provide one Class A circuit (NAC 3&NAC 4) or two Class B circuits (NAC 3 and NAC 4).

Each NAC circuit, whether Class A or Class B, has the following ratings:

AUX Power Output Range Channels configured to power non-NAC devices are rated special application 20V - 26.4V at 2A max, power-limited. Refer to NAC Power Output Modes for compatible devices.
Quiescent Current Consumption 30 mA
Maximum Current Consumption 50 mA (exclude current draw on outputs)
Current per NAC Output 2.5 A per channel, power-limited
Fuse (Electronic)

Average Current Limit: 1 to 2.5 A, programmable
Peak Current Limit: 3.0 A, fixed per channel

Supervision Reverse-polarity
End-of-Line Device Diode (S2029)
Short Circuit Threshold 130 Ohms +/- 20%
Maximum Line Impedance 4V loss (load-dependent)

Regulated NAC Outputs

NAC outputs operate in a regulated mode when conforming to specific levels of continuous or pulsed DC. NAC outputs meet requirements for regulated levels when the output current does not exceed the constraints described below.

Regulated Non-Pulsing Output Current

Currents cannot exceed 2.5A from any single NAC output:

Combined currents of all four NAC outputs cannot exceed 5A

System must not exceed maximum power supply output rating.

Regulated Pulsing Output Current

5.25A Power Supply - Regulated pulsing DC output = Max 500mA total across all NACs

10.25A Power Supply - Regulated pulsing DC output = Max 600mA from any NAC output, Max 2.4 A per Board

System must not exceed maximum power supply output rating.

Refer to Specifications for operating NAC outputs in the regulated mode.

Special Application NAC Outputs

NAC outputs can operate in a special application mode. NACs configured for special application have specific loading limitations, as detailed below.

Manufacturer Maximum No. of Devices per Channel Maximum Current Draw per Channel Power
Supply
Maximum Current Draw Across All NACs1
Amseco 27 2.4A S406 5.25A 2.5A
S408 10.25A 5A
Gentex 32 2.5A S406 5.25A 2.5A
S408 10.25A 5A
System Sensor 20 1.32A S406 500’S 2.1A
S408 10.25A 5A
Wheelock 41 2.5A S406 5.25A 2.5A
S408 10.25A 5A

1   When System Sensor is used in combination with any other manufacturer, the 2.1A limit applies across all NACs.

Refer to Specifications for operating NAC outputs in the special application mode.

AUX 24V

Terminal

Rating

AUX 24V (1)
OUT ( + ) and ( - )

Regulated 24 VDC @ 900 mA

AUX 24V (1)
RTN ( + ) and ( - )

Supervision only. Not an output.

AUX 24V (2)
OUT ( + ) and ( - )

Regulated 24 VDC @ 900 mA

AUX 24V (2)
RTN ( + ) and ( - )

Supervision only. Not an output.

Relay Ratings

Terminals

Connection

Ratings

(NO), (C), and (NC)

TROUBLE RELAY

  • Volt-free, Form C contacts
  • 30V DC @ 1 A maximum, Resistive
  • Programmable
  • ACTIVE during complete power loss
  • Not supervised

(NO), (C), and (NC)

FIRE RELAY
SUPERV RELAY
PROG 1 RELAY
PROG 2 RELAY

  • Volt-free, Form C contacts
  • 30V DC @ 1 A maximum, Resistive
  • Programmable
  • INACTIVE during complete power loss
  • Not supervised

Network (RS-485)

Terminal

Rating

W

Ground for cable shield (if applicable)

( + ), ( - ) IN

Data 3.3 V, current-limited

( + ), ( - ) OUT

Data 3.3 V, current-limited

RS-485 I/O

Terminal

Rating

W

Ground for cable shield (if applicable)

( + ), ( - ) IN

Reserved for future use.

( + ), ( - ) OUT

Data 3.3 V, current-limited

The RS-485 I/O utilizes standard RS-485 signaling in multi-drop mode with 120 Ohm terminations.

Fire Routing Output 1

Reserved for future use.

Prog Inputs

Terminals

Rating

1, 2, 3

Supervision: None
Open Circuit Voltage: 24 VDC
Activation: Short to 0V terminal (< 100 ohms)
Activation current: 3.3 mA typical

Fire Routing Input

Supervised input to receive confirmation signal from fire routing equipment. Reprogrammable for any input event type.

Terminals

Rating

( + ), ( - )

Supervision: Class B
Open Circuit Voltage: 10V
End-of-Line device: 3.3K Ohm resistor (S2063)
Activation device: 680 Ohm resistor

Fire Routing Output 2

Reprogrammable for any output event type.

Terminals

Rating

( + ), ( - )

Regulated 24V DC @ 60 mA
Fuse: Self-resetting
Supervision: Reverse-polarity DC
End-of-line device: Diode (S2029)

Prog Routing Input 1

Programmable for any input event type.

Terminals

Rating

( + ), ( - )

Supervision: Class B
Open Circuit Voltage: 10V
End-of-Line device: 3.3K Ohm resistor (S2063)
Activation device: 680 Ohm resistor

Prog Routing Output

Terminals

Rating

( + ), ( - )

24V max.
Impedance between (+) and (-) terminals measures 3.3K ohms when inactive.
Impedance between (+) and (-) terminals measures 680 ohms when active.

Prog Routing Input 2

Programmable for any input event type.

Terminals

Rating

( + ), ( - )

Supervision: Class B
Open Circuit Voltage: 10V
End-of-Line device: 3.3K Ohm resistor (S2063)
Activation device: 680 Ohm resistor

Trouble Routing Output

Reprogrammable for any output event type.

Terminals

Rating

( + ), ( - )

Regulated 24V DC @ 60 mA
Fuse: Self-resetting
Supervision: Load > 5 mA
End-of-line device: 3.3K ohms if load < 5 mA

Trouble Routing Input

Reprogrammable for any input event type.

Terminals

Rating

( + ), ( - )

Supervision: Class B
Open Circuit Voltage: 10V
End-of-Line device: 3.3K Ohm resistor (S2063)
Activation device: 680 Ohm resistor

 

System Information

Property

Description

Software Zones

2000 zone capacity

Software Groups

5000 group capacity

Event Log

10,000 event capacity, 1 second resolution. Filterable and printable.

Cause and Effects 5000

Mechanical

Fascia Components

Property

Description

Display

Full color 800 x 480 LCD with resistive touch screen and automatic backlight dimming

XT+ Printer

40 column, front loading thermal (optional)

Zone LED Indicators

Up to 3 banks of 48 (144) (optional)

Operating Environment

Dry indoor use only.

Temperature Range

23°F (-5°C) - 120°F (49°C)

Relative Humidity

Up to 95%, non-condensing

Cabinet Housing

Housing Description
Dimensions

4 Slot Standard Cabinet - 420mm (W) x 590mm (H) x 153mm (D), approximately 16.5in (W) x 23.2in (H) x 6in (D)

8 Slot Standard Cabinet - 540mm (W) x 720mm (H) x 160mm (D), approximately 21.3in (W) x 28.3in (H) x 6.3in (D)

4 Slot Deep Cabinet - 420mm (W) x 590mm (H) x 203mm (D), approximately 16.5in (W) x 23.2in (H) x 8in (D)

8 Slot Deep Cabinet - 540mm (W) x 720mm (H) x 212mm (D), approximately 21.3in (W) x 28.3in (H) x 8.3in (D)
Construction

 

Standard and Deep Cabinet Models

These models include:

  • Mild sheet steel enclosure, 1.2 mm
  • Removable equipment chassis
  • All epoxy powder coated
  • Knockouts top and back, one on each side
  • Hinged lid with single locks
  • Hinged bridge plates containing fascia indications
  • Optional printer
Finish Epoxy powder coated
Color Lid & Box - Red or Gray
Control Plate - RAL7016

Cable Entry

Standard and Deep Cabinet Models - 28 knockouts top, 19 knockouts back, 1 knockout each side
Mounting Minimum size #12, Maximum size #14. 40mm (1.5in.) length

This following figures illustrate the XT+ Extinguishant Control Panel cabinet housing options. All cabinets can be ordered with an optional second aperture to accommodate a printer or Fire In Zone LED indicators.

4 Slot Standard Enclosure

8 Slot Standard Enclosure

4 Slot Deep Enclosure

8 Slot Deep Enclosure